Storm Copper Logo and Home Page Link

 

Argentina Canada Chile Columbia Costa Rica Dominican Republic Ecuador France

Germany Spain Mexico Peru Puerto Rico United Kingdom (Great Britain) United States Venezuala

 

Storm Copper saves OEMs time and money by incorporating all fabrication processes under one roof.
OEM Copper Parts
Become A Fan!
 

OEM HOTLINE
1-800-394-4804

Copper Bus Tubing

Explore Storm Copper's Products and Services

Fabricated Copper Parts

OEM Copper Parts

Copper Bus Bar

Copper Ground Bars and Kits

Braided Flex Connectors

Laminated Bus Bar

Powder Coated Bus Bar

Ground Rods and Clamps

Battery Connectors & Straps


Copper Metal Distribution

Copper Sheet

Copper Bar

Copper Flashing

Copper Rod

Copper Tubing - Electrical

Copper Plate

Wholesale Copper Metal Products


Electrical Insulators

Standoff Insulators - Poly

Standoff Insulators - Ceramic

Standoff Insulators - Metric

Insulating Tape and Sheet


About Storm Copper

Our Bus Bar History

Directions To Our Plant

Art & Craft Copper Supplies

 

DUNS: 62-393-3397

NAICS: 332116
CAGE/NCAGE: 1Y2K0

C o n t a c t :

OEM Sales Manager
240 Industrial Park Lane,
Decatur, TN 37322
1-800-394-4804
FAX 423-334-3389

email: busbar@stormcopper.com

High-Conductivity Copper Bus Tubing - Alloy C10200

Standard Pipe Sizes, Hard Drawn, Schedule 40:

Nominal Dimensions, Inches
Cross Sectional Area of Copper
DC Resistance
60 Cycle Current Rating/Amperes
Indoor
Indoor
Outdoor
Pipe Size (In.)
Outside Diameter
Inside Diameter
Wall Thickness
Nominal Weight Lb/Foot
Square In.
Thousand Cir. Mils.
Microhms Per Foot, At 20 C, (68 F)
Skin Effect Ratio
30 C Rise
65 C Rise
65 C Rise
0.50
0.840
0.626
0.107
0.96
0.246
314
34.22
1.00
380
620
760
0.75
1.050
0.822
0.114
1.30
0.336
427
25.15
1.00
540
790
960
1.00
1.315
1.063
0.126
1.82
0.471
599
17.91
1.00
650
1000
1200
1.25
1.660
1.368
0.146
2.69
0.694
884
12.14
1.00
870
1350
1600
1.50
1.900
1.600
0.150
3.20
0.835
1050
10.22
1.00
1020
1550
1800
2.00
2.375
2.063
0.156
4.22
1.088
1385
7.75
1.01
1250
1950
2200
2.50
2.875
2.501
0.187
6.12
1.579
2011
5.34
1.01
1700
2550
2850
3.00
3.500
3.062
0.219
8.75
2.257
2874
3.73
1.02
2175
3300
3650
3.50
4.000
3.500
0.250
11.40
2.945
3750
2.86
1.02
2575
4000
4400
4.00
4.500
4.000
0.250
12.90
3.338
4250
2.51
1.02
2850
4500
4900
5.00
5.562
5.062
0.250
16.20
4.172
5312
2.00
1.02
3450
5500
6000
6.00
6.625
6.125
0.250
19.40
5.007
6375
1.67
1.03
4000
6400
7000
8.00
8.625
8.001
0.312
31.60
8.148
10370
1.03
1.05
5700
9100
9900
10
10.750
10.020
0.365
46.20
11.91
15160
0.7
1.11
7400
11900
12900
12
12.750
12.000
0.375
56.50
14.58
18550
0.58
1.12
8800
14000
15200

 

Extra-Strong, Hard Drawn, Schedule 80:

Nominal Dimensions, Inches
Cross Sectional Area of Copper
DC Resistance
60 Cycle Current Rating/Amperes
Indoor
Indoor
Outdoor
Pipe Size (In.)
Outside Diameter
Inside Diameter
Wall Thickness
Nominal Weight Lb/Foot
Square In.
Thousand Cir. Mils.
Microhms Per Foot, At 20 C, (68 F)
Skin Effect Ratio
30 C Rise
65 C Rise
65 C Rise
0.50
0.840
0.542
0.149
1.25
0.3235
412
26.06
1.00
420
710
880
0.75
1.050
0.736
0.157
1.71
0.4405
561
19.14
1.00
590
900
1100
1.00
1.315
0.951
0.182
2.51
0.6478
825
13.01
1.00
750
1200
1450
1.25
1.660
1.272
0.194
3.46
0.8935
1138
9.44
1.00
975
1550
1800
1.50
1.900
1.494
0.203
4.19
1.0820
1378
7.79
1.00
1150
1800
2100
2.00
2.375
1.933
0.221
5.80
1.4960
1904
5.64
1.01
1500
2300
2600
2.50
2.875
2.315
0.280
8.85
2.2830
2906
3.69
1.02
1975
3050
3400
3.00
3.500
2.892
0.304
11.80
3.0520
3886
2.76
1.03
2425
3800
4200
3.50
4.000
3.358
0.321
14.40
3.7100
4724
2.27
1.04
2875
4400
4800
4.00
4.500
3.818
0.341
17.30
4.4550
5673
1.88
1.05
3100
5100
5500
5.00
5.562
4.812
0.375
23.70
6.1110
7781
1.37
1.06
3850
6500
7000
6.00
6.625
5.751
0.437
32.90
8.4950
10820
0.98
1.13
4500
8000
8700
8.00
8.625
7.625
0.500
49.50
12.7500
16240
0.66
1.19
6500
10600
11500
10.00
10.750
9.750
0.500
62.40
16.1000
20500
0.52
1.22
8000
12900
14000

 

NOTE: Variations of these Copper Tubing values must be expected in practice.

IMPORTANT: The "Pipe Size" designation listed above does not directly correspond to the outside or inside diameter, review the above table very carefully to determine the appropriate diameter for your requirement. This is the cause of many installation problems in the field with High-Conductivity Copper Bus Tubing.

ASTM Specification B188 Seamless Copper Bus Pipe and Tube, establishes the outside diameters, the tolerances in terms of weight, and the electrical inspection. DC Resistance for hard drawn temper per ASTM-B188.

Skin-effect ratio of the copper tubing listed above at 60 cycles per second and 105 C temperature.

 