Glastic Standoff Insulators and SpacersFor grounding bar insulation, busbar standoffs and bus connectorsStorm Copper Components Co is a stocks most sizes of stand-off insulators produced by the Glastic Corporation. These insulators find applications as standoffs for grounding bars, busbar insulators, ground kits, bus connectors, panelboards, switchboards and buss bar applications. For Pricing and Availability Visit our Electrical Insulator Online Store or call - 800-394-4804 |








|
Part Number
|
Height
|
Thread Size
|
Suggested Indoor Voltage Rating |
Short Time Electrical Strength kV |
Weight/Pound
|
|
2165-1A
|
1"
|
1/4" X 20 X 5/16" DEEP
|
600
|
18.6
|
.06
|
|
2165-1B
|
1-1/4"
|
1/4" X 20 X 5/16" DEEP
|
600
|
----
|
.06
|
|
1603-2A
|
1-3/8"
|
3/8" X 16 X 3/8" DEEP
|
600
|
10.0
|
.19
|
|
1603-2D
|
1-3/8"
|
3/8" X 16 X 3/8" DEEP
|
600
|
10.0
|
.19
|
|
2015-1A
|
1-1/2"
|
1/4" X 20 X 1/2" DEEP
|
1500
|
33.4
|
.20
|
|
2015-2A
|
1-1/2"
|
5/16" X 18 7/16" DEEP
|
1500
|
33.4
|
.19
|
|
2015-3A
|
1-1/2"
|
3/8" X 16 X 3/8" DEEP
|
1500
|
33.4
|
.20
|
|
2015-2B
|
1-3/4"
|
5/16" X 18 7/16" DEEP
|
2000
|
---
|
.25
|
|
2015-3B
|
1-3/4"
|
3/8" X 16 X 3/8" DEEP
|
2000
|
---
|
.25
|
|
2015-2C
|
2"
|
5/16" X 18 X 7/16" DEEP
|
2300
|
43.1
|
.30
|
|
2015-3C
|
2"
|
3/8" X 16 X 9/16" DEEP
|
2300
|
43.1
|
.31
|
|
2015-4C
|
2"
|
1/2" X 13 X 5/8" DEEP
|
2300
|
43.1
|
.30
|
|
2015-3D
|
2-1/4"
|
3/8" X 16 X 9/16" DEEP
|
2700
|
---
|
.36
|
|
2015-4D
|
2-1/4"
|
1/2" X 13 X 5/8" DEEP
|
2700
|
---
|
.36
|
|
1461-1A
|
2-1/8"
|
3/8" X 16 X 9/16" DEEP
|
2500
|
49.3
|
.61
|
|
1461-1B
|
2-1/8"
|
1/2" X 13 X 5/8" DEEP
|
2500
|
27.9
|
.61
|
|
1461-1C
|
2-1/8'
|
5/8" X 11 X 5/8" DEEP
|
2500
|
21.0
|
.61
|
|
1872-1A
|
2-1/2"
|
3/8" X 16 9/16" DEEP
|
3200
|
51.4
|
.44
|
|
1872-2A
|
2-1/2"
|
1/2" X 13 X 5/8" DEEP
|
3200
|
51.4
|
.45
|
|
1872-3F
|
2-5/8"
|
5/8" X 11 X 11/16" DEEP
|
3400
|
---
|
.60
|
|
1872-1B
|
2-3/4"
|
3/8" X 16 X 9/16" DEEP
|
3600
|
---
|
.53
|
|
1872-2B
|
2-3/4"
|
1/2" X 13 X 5/8" DEEP
|
3600
|
---
|
.51
|
|
1872-1C
|
3"
|
3/8" X 16 X 9/16" DEEP
|
4100
|
---
|
.59
|
|
1872-2C
|
3"
|
1/2" X 13 X 5/8" DEEP
|
4100
|
---
|
.60
|
|
1872-1D
|
3-1/4"
|
3/8 X 16 X 9/16" DEEP
|
4500
|
---
|
.67
|
|
1872-2D
|
3-1/4"
|
1/2" X 13 X 5/8" DEEP
|
4500
|
---
|
.67
|
|
1872-1E
|
3-1/2"
|
3/8" X 16 X 9/16" DEEP
|
5000
|
55.2
|
.76
|
|
1872-2E
|
3-1/2"
|
1/2 X 13 X 5/8" DEEP
|
5000
|
55.2
|
.58
|
|
1872-3E
|
3-1/2"
|
5/8" X 11 X 11/16" DEEP
|
5000
|
55.2
|
.74
|
|
2035-1
|
3-1/2"
|
2" BOLT CIRCLE
|
5000
|
---
|
1.20
|
|
1642-10E
|
3-1/2"
|
3/8" X 16 X 9/16" DEEP -
2" BOLT CIRCLE
|
5000
|
---
|
1.78
|
|
2450-15
|
6"
|
3/8" X 16 X 9/16" DEEP -
2" BOLT CIRCLE
|
15,000
|
---
|
3.49
|
Glastic Standoff Insulator Specfications
|
VALUES
|
STYLES
|
||||||||
|
2165
|
1603-2A
|
1603-2D
|
2015
|
1461
|
1872
|
2035-1
|
1642-10-E
|
2450-15
|
|
|
Tensile Strength (lbs.)
|
1,000
|
2,000
|
2,500
|
2,000
|
3,000
|
2,500
|
2,500
|
3,000
|
5,000
|
|
Cantilever Strength (inch lbs.)
|
400
|
1,500
|
1,800
|
1,650
|
3,500
|
3,000
|
3,600
|
6,000
|
10,000
|
|
Compression Strength (lbs.)
|
8,000
|
20,000
|
20,000
|
20,000
|
60,000
|
25,000
|
25,000
|
20,000
|
20,000
|
|
Torgue Strength (ft. lbs.)
|
12
|
25
|
30
|
50
|
50
|
50
|
---
|
200
|
285
|
|
Arc Resistance (sec.)
|
180
|
180
|
180
|
180
|
180
|
180
|
180
|
180
|
180
|
|
UL Subject 94 Flame Resistance
|
94 V-0
|
94 V-0
|
94 V-0
|
94 V-0
|
94 V-0
|
94 V-0
|
94 V-0
|
94 V-0
|
94 V-0
|
|
Height Tolerance (in.)
|
+/- .015
|
+/- .015
|
+/- .015
|
+/- .015
|
+/- .015
|
+/- .015
|
+/- .015
|
+/- .015
|
+/- .015
|
|
Creep Distance (in.)
|
Insulator Height |
1-5/8
|
1-5/8
|
1/4 Plus Insulator Height
|
3-1/4
|
5/16 Plus Insulator Height
|
3-1/2
|
3-11/16
|
7
|
|
Dry Hi-Pot (volts) NEMA Specs.
|
---
|
---
|
---
|
---
|
---
|
---
|
---
|
19,000
|
36,000
|
|
Dew Hi-Pot (volts) NEMA Specs.
|
---
|
---
|
---
|
---
|
---
|
---
|
---
|
15,000
|
26,000
|
|
Impulse (volts, 1.5 x 40 wave)
|
---
|
---
|
---
|
---
|
---
|
---
|
---
|
60,000
|
95,000
|
|
Track Resistance (minutes)
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
600
|
Glastic Standoff Insulator email info
C o n t a c
t :
Sheila Amburn-Stone
240 Industrial Drive
Decatur, TN 37322
1-800-394-4804
423-334-3389 Fax
Email Glactic Standoff Insulators@stormcopper.com
Product Index:Ampacity TablesBattery ConnectorsBusbarCopper BarCopper SpecificationsElectrical StandoffInsulatorsGlastic Standoff InsulatorsGround BarsGrounding Kits |
Busbars Home | News | Search | Products |Send Prints | Bus Bar Design |Questions about Glastic Standoff Insulators
The following disclaimer is in the bottom margin of the literature where this information was taken: All of the information, suggestions, and recommendations pertaining to the properties and uses of the Glastic products described herein are based upon tests and data believed to be accurate; however, the final determination regarding the suitability of any material described herein for the use contemplated, the manner of such use, and whether the use infringes any patents is the sole responsibility of the user. There is no warranty, express or implied, including, without limitation warranty of merchantability or fitness for a particular purpose. Under no circumstances shall we be liable for incidental or consequential loss or damage. Naturally Storm Copper Components, Co. adopts the same position regarding liability.
Glastic is a registered trademark of Glastic Corporation.
For more information call toll free 800-394-4804